What size generator do you need?
Tick what has to run at the same time. This adds up the running and starting watts from Honda's and Champion's charts and says which size of portable generator covers them. It's arithmetic, not a test.
This page has no store links. The pages it links to carry disclosed affiliate links.
Generator safety: carbon monoxide and backfeed
Carbon monoxide: never run a generator indoors, in a garage, basement or crawlspace, or near windows, doors or vents. Using a generator indoors can kill you in minutes. Use battery-powered carbon monoxide alarms in the home. CPSC Safety Alert 5123
Backfeed: never plug a generator into a wall outlet or a dryer outlet. That is extremely dangerous: it can energize utility lines and injure line workers and people in the home. Use a transfer switch or interlock installed by a licensed electrician. CPSC Safety Alert 5123 (PDF)

How it's worked out
running W = every ticked load's running watts, added upstarting W = running W + the largest single startor, if loads may start together: running W + every start
The result above starts with a top-freezer fridge, a gas furnace blower and a sump pump: Running: 400 + 875 + 800 = 2,075 W. Starting: 2,075 W running + 2,350 W, the largest single start (Gas furnace blower, 1/2 hp) = 4,425 W.
Why only the largest start counts
A motor or compressor draws far more for two or three seconds as it starts. Generac's page on starting watts says to add up the running watts of everything you'll run at once and make sure the generator can also supply the highest single start. This page adds that start on top of the running total, which errs large. Honda's chart gives a load with no motor the same figure in both columns, so its starting figures may already include the running watts, and then the sum counts the starting load's running watts twice. Honda's power management page says to start big loads at different times, so only one start happens at once. A load with no motor, like a space heater, needs no extra starting watts: Champion's chart says to size those on running watts only.
Where the figures come from
Each preset is from Honda's wattage chart or Champion's, read on Nov 10, 2026. Where they differ, the preset is the higher figure, so the result errs large. Champion gives ranges; the preset is the top of the range. The kettle is from the runtime table.
The sizes come from generators we cover: the Honda EU2200i gives 1,800 W running and 2,200 W maximum, and the Westinghouse iGen5000DFc 3,900 W running and 5,000 W peak on gasoline. All of them have 120 V outlets only.
What it leaves out
- Margin. Neither Honda's chart nor Champion's states a margin to add on top, so the result is the minimum. To leave room, add a "Something else" row.
- Altitude and heat. A generator gives less power high up and in hot weather. Its manual gives the derating.
- Fuel. How long a tank lasts is in How Much Gas Does a Portable Generator Use in a Day?.
- Wiring. A 240 V load or anything hard-wired needs a transfer switch or interlock installed by a licensed electrician. See Never Backfeed Your Generator: Use a Transfer Switch Instead and Transfer Switch Permits: Do You Need One and an Electrician?.
If a medical device has to stay on, ask your medical provider and the device's maker what they recommend. This page isn't medical advice.
Sources
- Honda, What Wattage Generator Do I Need?
- Honda, Generator Power Management
- Champion, Generator Wattage Chart
- Generac, What Does Surge/Starting Wattage Mean?
- Generac, What Size Generator Do I Need?
- Generator outputs: the product pages behind our inverter generator picks.
Every preset and where it comes from
- Top-freezer fridge, 16 to 20 cu ft: 400 W running, 1,200 W starting. From Champion's chart and Honda's chart.
- Bottom-freezer fridge, 25 to 29 cu ft: 400 W running, 1,200 W starting. From Champion's chart and Honda's chart.
- Chest freezer: 500 W running, 1,200 W starting. From Champion's chart and Honda's chart.
- Gas furnace blower, 1/2 hp: 875 W running, 2,350 W starting. From Honda's chart.
- Window air conditioner, 10,000 BTU: 1,500 W running, 2,400 W starting. From Honda's chart and Champion's chart.
- Central air conditioner, 3 ton: 3,500 W running, 6,000 W starting, 240 V. From Champion's chart.
- Space heater: 1,500 W running, no extra starting watts. From Champion's chart.
- Sump pump, 1/3 hp: 800 W running, 1,600 W starting. From Honda's chart and Champion's chart.
- Well pump, 1/2 hp: 1,000 W running, 2,000 W starting, 240 V. From Champion's chart.
- Electric water heater: 4,500 W running, no extra starting watts, 240 V. From Honda's chart and Champion's chart.
- Washing machine: 1,200 W running, 2,300 W starting. From Honda's chart and Champion's chart.
- Electric clothes dryer: 6,000 W running, 6,750 W starting, 240 V. From Champion's chart and Honda's chart.
- Electric range, one burner: 2,400 W running, no extra starting watts, 240 V. From Champion's chart and Honda's chart.
- Microwave, 1,000 W: 1,500 W running, no extra starting watts. From Honda's chart.
- Coffee maker, 4 cup: 600 W running, no extra starting watts. From Honda's chart.
- Electric kettle, while heating: 1,500 W running, no extra starting watts. From the runtime table.
- Modem and Wi-Fi router: 20 W running, no extra starting watts. From Champion's chart.
- Laptop: 250 W running, no extra starting watts. From Honda's chart.
- TV, 32 to 55 inch: 400 W running, no extra starting watts. From Champion's chart.
- LED lights, 10 bulbs: 150 W running, no extra starting watts. From Champion's chart.
For a battery instead of a generator, use the power station size calculator. For a UPS, use the UPS runtime calculator.